Your Cart is empty!
Condition: New with Warranty Brand: REO UK Ltd, Range: Input Choke
4% AC Line Choke to 160A Three Phase.Connect to the mains input of a 3ph AC Inverter Drive to increase protection from mains transients, reduce harmonic current (THD) and reduce the RMS load.Recommended for an Inverter Drive connection to a high fault level low impedance supply, where sliding contacts on busbars are present and where the incoming power supply is prone to spikes, dips notches or other disturbances.
Current Rating: 160A.Overload: 1.5 x for 60 seconds onece per hour.Voltage: up to 500V 3 phase Inductance: 0.180mH.Power Loss: 145W.Protection: IP00.Dimensions: 240mm x 175mm x 210mm High.Weight: 22kg.Standards: EN 60289 / EN 61558
Also known as: Mains Choke, Line Reactor, AC Choke, AC Inductor or Input Choke.
Part Number: NCNW903/160.
NCNW905/160
(201020905004200)
Order code: 38334
Delivery 14 weeks
We've sent you a message containing a confirmation link. Click the link to complete the process.