Danfoss iC2-Micro AC Frequency Inverter for 0.75kW 230V 3 Phase Motor in V/F or Sensorless Vector Control (VVC) to 4.2A.
Output Current Rating: 4.2A
Overload: 150% x 60 seconds.
Size: MA01c - 70mm Wide x 143mm Deep x 150mm High. IP20.
Weight: 1kg.
Speed Control Range: 0-200 Hz (VVC+), 0-400 Hz (VxF).
Braking (DBr): Not fitted
Fixed Keypad with front mounted Potentiometer.
2 x Analogue Inputs, 5 x Digital Inputs, 1 x Analogue Output, 1 Digital Output, 1 x Relay Contact set.
Communications: RS485 (twin-wire); FC Protocol, Modbus RTU.
Programmable from a PC using Danfoss MyDrive. (via RS485 input or RJ45 with converter not direct)
Additional Keypad available for Panel Mounting (via RJ45). See linked products below.
Input Current: 11.6A max
Input Voltage: 200-240V (+10%, -15%) at 50-60Hz (±5%)
EMC Filters: To IEC/EN 61800-3 1st Environment – C1
Cubicle mount.
Ambient: Rated at 50°C
Ventilation space above and below: 100mm.
Ventilation space at sides: 0mm (drives can be mounted side by side)
Heat Loss at max output: 31W.
Mounting: Via 3 x M4 Fixings at rear on 140.4mm x 55mm centres
Full part number: IC2-30FA1N0204A2E20F0+ACXX
Type Code: 132L6111
Previous Generation: 132F0003: FC-051PK75S2E20H3