Danfoss iC2 Micro 3kW 400V 3ph AC Inverter Drive, DBr, C2 EMC

132L6132 (IC2-30FA3N0407A2E20F2+ACBC)

Order Code: 39506
Available to Order
Delivery 3-5 working days
£551.00
(excl. VAT)
£661.20
(inc. VAT )
Price break
per unit
1+
£551.00

Condition: New with Warranty
Brand: Danfoss, Range: iC2

Danfoss iC2-Micro AC Frequency Inverter for 3kW  400V 3 Phase Motor in V/F and Sensorless Vector Control (VVC) to 7.2A.

Output Current Rating: 7.2A
Overload: 150% x 60 seconds.

Size: MA02a - 75mm Wide x 175mm Deep x 186mm High. IP20.
Weight: 1.6kg.

Speed Control Range: 0-200 Hz (VVC+), 0-400 Hz (VxF).
Braking (DBr): Internal Brake Switch Fitted. Minimum Resistance: 100Ω. An external Braking resistor is required if Dynamic Braking option is used; see linked items below. 

Fixed Keypad with front mounted Potentiometer.
2 x Analogue Inputs, 5 x Digital Inputs, 1 x Analogue Output, 1 Digital Output 1 x Relay Contact set.
Communications: RS485 (twin-wire); FC Protocol, Modbus RTU.
Programmable from a PC using Danfoss MyDrive. (via RS485 input or RJ45 with converter not direct)

Input Current: 11.5A max
Input Voltage: 380-480V (+10% -15%) at 50-60Hz (±5%)
EMC Filters: To IEC/EN 61800-3 2nd Environment (Industrial); 1st Environment with restrictions – C2

Cubicle mount.
Ambient: Rated at 50°C
Ventilation space above and below: 100mm.
Ventilation space at sides: 0mm (drives can be mounted side by side)
Heat Loss at max output: 58W.
Mounting: Via 4 x M4 Fixings at rear on 176.4mm x 59mmcentres

Full part number: IC2-30FA3N0407A2E20F2+ACBC
Type Code: 132L6132

Previous Generation:132F0024; FC-051P3K0T4E20H3 

You may also be interested in...

Photo of Dynamic Brake Resistor, 100 Ohms x 800 Watts

Dynamic Brake Resistor, 100 Ohms x 800 Watts

EST-100R-SB

Order code: 33710

Delivery 2 weeks

£108.00
1+
Photo of Danfoss iC2 Micro Remote Control Panel (Keypad), OP2

Danfoss iC2 Micro Remote Control Panel (Keypad), OP2

132G0234

(2.0 OP2)

Order code: 39515

2 in stock

3+ normally 3-5 days

£38.00
1+