Vacon 100 Series AC Industrial Inverter for 55kW (75HP) 400V 3 Ph motor in VxF or Sensorless Vector control to 105A at high overload, or 75kW (90HP) to 140A when Fan/Pump rated. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Size MR8: 290mm Wide x 343mm Deep x 996mm High. IP21/NEMA Type 1
Weight: 66kg.
Output: 105A (High Overload: 150% x 60 seconds every 10 minutes, 200% x 2 seconds every 20 seconds).
Output Current: 145A (Low Overload (Fan/Pump mode): 110% x 60 seconds every 10 minutes, 200% x 2 seconds every 20 seconds).
Speed Control Range: 0-320Hz.
Braking: Minimum 6.5 Ohm external resistor (not supplied).
Graphical keypad.
2 x Analogue Inputs, 6 x Digital Inputs, 1 x Analogue Output, 2 x Relay Contact set, RS485.
Input Current: [as output current]
Input Voltage: 380-500V -10%/+10% Three Phase at 50-60Hz (± 10%)
EMC Filters: IEC EN61800-3 Category C2 1st Environment (Industrial and Domestic), or remove jumpers for use connected to an IT Supply.
Options:
B Slot: F3,3 Relay board
C Slot: B4,AI,2AO(mA,isol),+24V/EXT
D Slot: No board
E Slot: BJ,STO, ATEX therm
ATEX: II (2) GD
Fieldbus: Std protocol,Modbus,N2,BacNet
Wall mount in clean environment or cubicle mount.
Rated 40°C Ambient.
Ventilation space in above: 350mm
Ventilation space below: 100mm
Ventilation space at sides: 20mm
Heat Loss at max output: [not specified]
Mounting via 6 x 9mm diameter holes at rear.
Manufacturer part number is VACON0100-3L-0140-5+SCB4+SEBJ+FL05+DPAP+DLDE.
Vacon 100 replaces NXS Series.
Download the Vacon 100 Manual from the link below:-