Danfoss VLT FC-302 series AC Frequency Inverter for 200kW (300HP) in High Overload or 250kW (335HP) in Pump/Fan mode. 525V-690V three phase motor in VxF control or Sensorless Flux control to 256A/303A.
Converts fixed frequency three phase 690Vac input to variable frequency three phase 690V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
***Please check that these are the correct parts. Special factory order and is non-returnable.***
Frame Size D4H: 1122mm high x 350mm wide x 375mm deep. IP20.
Weight: 125kg.
Continuous Output Current: 303A (High Overload), 400A (Normal Overload).
High Overload: 160% for 60 seconds every 10 minutes. Normal Overload: 110% for 0.5 seconds every 10 minutes.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300 Hz in Sensorless Flux Control.
Braking: Not Fitted.
Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Programmable Relay Outputs, Terminals for RS485 Communications.
1 x Safe Torque Off Input, Catagory 3 to SIL2, SILCL2, performance level "d".
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
Slot A Option: Profibus DP MCA 101.
Mains option : Loadsharing
Input Voltage: 525-690Vac Three Phase ±10% at 50-60Hz ±5%.
EMC Compliant to Class A1 (C2) Commercial Environment.
Cubicle mount.
Ventilation space above and below should be 200mm.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Part number: 134G6799.
Type Code is: FC-302N200T7E20H2XGCXXXSXXXXA0BXCXXXXDX.