Danfoss VLT AutomationDrive FC 300 Series AC Frequency Inverter for 37kW/50HP in Heavy Duty mode to 73A and 45kW/ 60HP in Pump & Fan mode to 80A.
Enclosure C3: 550mm High x 308mm Wide x 333mm Deep.
IP20.
Weight: 35.7kg.
Overload - 150% x 60 seconds in Heavy Duty, 110% x 60 seconds in Fan/Pump mode.
No HMI Fitted.
Brake Switch, Not Fitted.
2 x Analogue Inputs, 4 x Digital Inputs, 1 x Analogue Output, 2 x Digital Outputs, 1 x Relay Contact set, FC Protocol, Modbus RTU.
Programmable from a PC via Danfoss MCT 10 Software
Option Slot A: Profibus DP.
Option Slot B: None.
Option Slot C: None.
Option Slot D: MCB-107 24V DC backup.
Input Current - 66A.
Input Voltage - 380-500V Three Phase ±10% at 50-60Hz.
EMC Filters to IEC/EN 61800-3 2nd Environment (Industrial) Class A2(C3) 25M
Wall mount in clean environment or cubicle mount.
Rated at 40°C Ambient.
Ventilation space above and below - 100mm.
Ventilation space at sides - 0mm (drives can be mounted side by side)
Heat Loss at max output - 1400W.
Mounting via 4 x 5mm diameter holes at rear on 59mm x 166.4mm centres
Full part number is - 131H7260.
String Code is: FC-302P37KT5E20H1XXXXXXSXXXXA0BXCXXXXD0.
Download the Danfoss VLT AutomationDrive FC 300 Manual from the link below:-