Danfoss VLT FC-302 series AC Frequency Inverter for 7.5kW (10HP). 400V three phase motor in VxF control or Sensorless Flux control. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Keypad fitted.
Frame Size: A3 268mm High x 130mm Wide x 205mm Deep.
Weight: 7kg
Supply Voltage: 380Vac - 500Vac +/- 10%, 50/60Hz +/-5%.
Input current (380 - 440V): 1.2A continuous, 1.9A intermittent.
Input Current (441-500VAC): 1.0continuos, 1.6A intermittent.
Continuous Output Current (380-440VAC): 14.4A, 23A intermittent.
Continuous Output Current (441-500VAC): 13.0A, 20.8A intermittent.
Overload: 160% for 60 seconds every 10 minutes.
Output frequency: 0 - 590Hz in V/F mode or 0 - 300Hz in Sensorless Flux Control.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300Hz in Sensorless Flux Control.
2 x Analogue Inputs, 6 Digital Inputs, 1 Analogue outputs, 2 Digital/Pulse outputs, 2 Relay Outputs.
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
Braking: 50 Ohms minimum resistance, 0.7kW nominal power for emergency stop and occassional stopping.
Option C1: MCB-107 24V DC Backup.
EMC Compliant to C3, Industrial Environment.
Cubicle mount.
Ventilation space above and below should be 100mm. Can be mounted flush to each other at either side.
Mounted on 4 x 5.5mm holes 257mm x 110mm apart.
Heat Loss is 255W at full load.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Full part number is 131B3244
Typecode: FC-302P7K5T5E20H2XGXXXXSXXXXAXBXCXXXXD0