WEG CFW11 Series AC Inverter with Safe Torque Off feature for 315kW (420HP) 400V 3 Ph motor to 560A at high overload, or 400kW (530HP) to 720A when Fan/Pump rated. Operates in VxF, Sensorless Vector or Full Closed-loop Flux Vector. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC induction motor or permanent magnet synchronous motor.
Dimensions: Frame G, 535mm Wide x 426mm Deep x 1265mm high.
Enclosure: IP20.
Weight: 215kg.
315kW, 560A with 150% overload for 60 seconds every 10 minutes, 200% for 3 seconds every 10 minutes - Change P0298 to 1
400kW, 720A with 110% overload for 60 seconds every 10 minutes, 150% x 3 seconds every 10 minutes - Default Rating
Speed Control Range: 0-300Hz (depending on control mode).
Braking: Optional via external Dynamic Braking Module (see linked products below).
Features: 2 Analogue Inputs, 6 Digital Inputs, Safe Torque Off terminals, 2 Analogue Outputs, 3 Relay Contact sets, USB Port (Type B), Real time clock.
DC Bus terminals available for DC supply, or common bus energy saving applications.
Programmable from a PC via USB cable and free 'G2 Superdrive' software.
Input Current: 560A at High Overload, or 720A when Fan/Pump Rated, via 2 x 710A High Speed fuses per phase.
Input Voltage: 380V to 480V Three Phase +10% -15% at 50-60Hz ±3%.
Internal DC Link Choke Included
EMC Filter: Integrated, to IEC EN61800-3 Category C3 (industrial)
Safety Function: Safe Torque Off (STO) suitable in applications up to Cat. 3 / PL d acc. to EN ISO 13849-1 and SIL 2 acc. to IEC 62061 / IEC 61508
Suitable for wall mount in a clean environment, cubicle mount or flange mount (through panel mounting - suitable for harsh environments).
Ambient Temperature: Rated 40°C.
Cubicle or Wall Mounted:
Ventilation Space: 20mm in front, 150mm above, 250mm below and 80mm at sides.
Heat Loss: 2191W at High Overload, or 2727W when Fan/Pump rated.
Mounting via 6 x M10 bolts at rear on 400mm x 1225mm centres.
Flange Mounted (through panel mounting)
This unit is supplied suitable for through panel mounting. There are mounting supports (metal plates) for cubicle mounting and hoisting eyes attached to the heatsink; these need to be removed when through panel mounting; no additional parts required.
Backplate Aperture: 495mm Wide x 1182mm High. Heatsink Depth (behind backplate) 202mm
Secure to backplate via 4 x M10 bolts on 400mm x 1220mm centres. Maximum thickness of backplate is 3mm
Heat Loss; Total losses (losses without heatsink): 2191W (591W) at High Overload, or 2727W (669W) when Fan/Pump rated.
Ventilation Flow required for adequate heatsink cooling: 19.3 m³/min
Extended Warranty Available: When purchased with a WEG W22 Motor the warranty for the motor and the AC Inverter can be extended to 3 years. Terms and Conditions apply, registration process is required.
Part Number : CFW11 0720 T4 OYZ, CFW110720T4OYZ Internal code is 11317617.
Replaces part number: CFW11 0720 T4 SZ, CFW110720T4SZ. (Code 11374925).
Download the WEG CFW11 Manual, Parameter Reference and Programming Guide from the links below:-